 pcflo version 4.3.        
 U.T. Austin Power System Engineering                                                                                    
 capabilities =   500 busses,  1500 lines and transformers
 read options file
 *** message code    28 ***
 impedance scan the following busses
 scan all busses
 harmonics calc. for harmonics  1 through 14,
 newton-raphson loadflow calculation, with gauss-seidel start
 (avg. p-q mismatch for switch over to newton-raphson =    .50000000 pu,
 acceleration factor =  1.20, gauss-seidel voltage update limit =    .0050 pu)
 zscan for sequence = 1.
 use r-only harmonics model for linear pq loads
 read bus data (first pass)

 Impedancia Z(f): IPUSA                                                                                                  , pcflo version = 4.3.        

 bus data - pu  (percent voltage, power)
  bus  name         type     p gen    q gen   p load   q load  voltage  q shunt    qgmax    qgmin area  rem.bus
  999   SWBUS31KV      1       .00      .00      .00      .00   103.00      .00      .00      .00    0        0
 *** message code    16 ***
 grounded wye connection assumed
   10   BAUTE          3       .00      .00      .00      .00      .00      .00      .00      .00    0        0
    1   BATP01         3       .00      .00     4.00     3.00      .00    -3.00      .00      .00    0        0
 *** message code    16 ***
 grounded wye connection assumed
 *** message code    16 ***
 grounded wye connection assumed
    2   BATP02         3       .00      .00    16.00     8.00      .00   -11.00      .00      .00    0        0
 *** message code    16 ***
 grounded wye connection assumed
 *** message code    16 ***
 grounded wye connection assumed
    3   BATP03         3       .00      .00    15.00    14.00      .00    -8.00      .00      .00    0        0
 *** message code    16 ***
 grounded wye connection assumed
 *** message code    16 ***
 grounded wye connection assumed
    4   BATP04         3       .00      .00     4.00     3.00      .00    -7.00      .00      .00    0        0
 *** message code    16 ***
 grounded wye connection assumed
 *** message code    16 ***
 grounded wye connection assumed
    0                  0       .00      .00      .00      .00      .00      .00      .00      .00    0        0
 number of busses =     6, number of pv busses =     0,
 number of remote controlled voltage busses =        0
 read line and transformer data (first pass)

 Impedancia Z(f): IPUSA                                                                                                  , pcflo version = 4.3.        

 line and transformer data - pu  (r,x and c in percent, tap in per unit, phase shift in degrees)
 from    to                                                                                               control control  control
                                                          tmin or   tmax or  tstep or                                     power or
  bus   bus ckt        r1        x1        c1    rating      amin      amax     astep       tap  phse shft    bus    side  voltage
  999    10   1       .60      5.80       .00        0.    .00000    .00000    .00000    .00000       .00       0       0       .0
 *** message code    13 ***
 zero sequence data not specified.  will not be able to perform zero
 sequence fault or harmonic analyses.  only one message of this type will appear.
   10     1   1     20.00     75.00       .00        0.    .95000   1.05000    .02500   1.00000       .00       0       0       .0
 *** message code    14 ***
 transformer connection type is assumed to be grounded wye - grounded wye
   10     2   1     14.00     29.00       .00        0.    .95000   1.05000    .02500   1.00000       .00       0       0       .0
 *** message code    14 ***
 transformer connection type is assumed to be grounded wye - grounded wye
   10     3   1     13.00     30.00       .00        0.    .95000   1.05000    .02500   1.00000       .00       0       0       .0
 *** message code    14 ***
 transformer connection type is assumed to be grounded wye - grounded wye
   10     4   1     14.00     30.00       .00        0.    .95000   1.05000    .02500   1.00000       .00       0       0       .0
 *** message code    14 ***
 transformer connection type is assumed to be grounded wye - grounded wye
    0     0   0       .00       .00       .00        0.    .00000    .00000    .00000    .00000       .00       0       0       .0
 number of lines  =     1, number of transformers =     4,
 number of voltage regulating transformers =     0
 number of phase regulating transformers =     0
 order busses according to method 2

 end of starting estimates

 Impedancia Z(f): IPUSA                                                                                                  , pcflo version = 4.3.        

 loadflow iteration summary
            absolute active power mismatch    absolute reactive power mismatch
                                     worst                               worst
 iteration       average     worst     bus           average     worst     bus

         0         10.66     19.00       2             12.95     51.18      10
 (nr)    1           .28       .55      10               .91      2.91      10
 (nr)    2           .00       .00      10               .00       .01      10
 (nr)    3           .00       .00      10               .00       .00       2

 Impedancia Z(f): IPUSA                                                                                                  , pcflo version = 4.3.        

 Impedancia Z(f): IPUSA                                                                                                  , pcflo version = 4.3.        
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent
 jacobian fill factor =     .0 percent

 Impedancia Z(f): IPUSA                                                                                                  , pcflo version = 4.3.        
 end of run